Untied Rubber Bellows - Type JP05JP03 Rubber Bellow

High Temperature Water.

Now Available With Precision Flt Flexible Lagging Jackets To Suit JP05

Specification

Untied E.P.D.M. rubber bellows with high tensile cord reinforced body and steel reinforced collar. Fitted with zinc plated carbon steel swivel flanges. Drilled to BS. 4504 NP16.

Application

Stourflex untied rubber bellows are designed to accommodate misalignment and both axial and lateral movement. They are also used to reduce noise and vibration from pumps and reciprocating machinery. The high tensile cord reinforced body allows the JP05 to be used on heating systems and engine cooling applications or where extended service life is required.

Maximum working temperature 105ºC. (Intermittent peaks up to 120°C) Maximum working pressure 16 Bar. Maximum working pressure at 105°C = 6 Bar Maxiumum working pressure at 90°C - 10 Bar.

Stourflex rubber bellows should not be used at both their maximum working temperature and pressure respectively. Maximum test pressure = 1.5 x working pressure or 1.5 x flange rating, whichever the lower.

Lagging

Stourflex are now able to offer a tailor-made flexible lagging jacket to help reduce heat losses on LTHW systems and heat gains & condensation on CHW systems. Please ask for more information.

 

Part Number N.B. Installed Length Movement Pressure
 (mm)
(mm)

Compression (mm)

Extension
(mm)

Lateral (mm)

Angular Working Pressure up to 60° (bar)
Vacuum Without Suuport Ring (mm Hg) Vacuum WithSuuport Ring (mm Hg)
 JP05-32-16 32 130 15 15 10 15° 16 500 750
 JP05-40-16 40 130 15 15 10 15° 16 450 750
 JP05-50-16 50 130 15 15 10 15° 16 450 750
 JP05-65-16 65 130 15 15 10 15° 16 350 750
 JP05-80-16 80 130 15 15 10 15° 16 350 750
 JP05-100-16 100 130 15 15 10 10° 16 300 600
JP05-125-16 125 130 15 15 10 10° 16 250 600
JP05-150-16 150 130 15 15 10 10° 16 250 600
JP05-200-16 200 130 15 15 10 16 200 500
JP05-250-16 250 130 15 15 10 16 100 500
JP05-300-16 300 130 15 15 10 16 100 500

 

  • Supplied length may vary. Tolerance +/- 5%
  • The movements stated above have been reduced to cater for high temperature applications
  • Where vacuum conditions or pressures and temperatures above those stated exist, please check with us the suitability of and effects on the service life Stourflex products. Vacuum suuport ring fitted upon request.
  • Details on larger sizes and alternative flange specifications are available on request
  • Stourflex products should be installed in accordance with our fitting instructions.
  • Stourflex rubber bellows should be periodically inspected and replaced if any deterioration is evident.
  • The JP05 rubber bellows are producted within the E.E.C and are stamped with date of manufacture. The JP05 conforms with and is certified to DIN 4809.

 

Download: Data Sheet and Installation Guide

Tel: 01384 393329

Email: This email address is being protected from spambots. You need JavaScript enabled to view it.